Soundproofing of a district heating plant

Soundproofing of a new district heating plant built in Alessandria, managed by Alessandria Calore S.r.l.

The gas-fired plant includes the installation of a 2.6 MW cogeneration unit, 4 condensing boilers, heat exchangers, compressors, transformers, electrical panels, and electric pumps connected to the district heating network.

The plant is located on Via Gandolfi, in an area bordering the railway on one side and residential buildings of 4–5 floors on two other sides.

According to the municipal acoustic zoning plan, the intervention area falls within the railway buffer zones (Class IV), while the nearest buildings are also partially within these buffer zones and partially outside them, being classified as Class II and III.

In addition to compliance with zoning limits, the differential criterion must also be verified at the adjacent residential indoor environments.

To obtain the necessary prior construction authorizations, a predictive acoustic impact assessment was prepared. This study, considering the pre-operational condition and the planned noise sources, defines detailed requirements point by point to ensure that the plant, at full operation, complies with the acoustic limits established by current legislation.

Immission limit values for Class II:

Land use classification (Presidential Decree 14/11/1997, Art. 3)

Reference time periods

Daytime (6:00–22:00)CLASS II – 50 dB
Night-time (22:00–6:00)CLASS II – 40 dB
Daytime (6:00–22:00)CLASS II – 55 dB
Night-time (22:00–6:00)CLASS II – 45 dB

Emission limit values for Class II:

Land use classification (Presidential Decree 14/11/1997, Art. 3)

Reference time periods

Daytime (6:00–22:00)CLASS II – 50 dB
Night-time (22:00–6:00)CLASS II – 40 dB
Daytime (6:00–22:00)CLASS II – 55 dB
Night-time (22:00–6:00)CLASS II – 45 dB

Solution

The works carried out were varied and involved all areas of the plant.

The work involved every room:

  • from ventilation silencers to the sound-absorbing lining of the engine room walls
  • from sound-insulating partitions to acoustic louvers of the heating plant
  • from acoustic doors to removable infill panels for extraordinary maintenance operations
  • each element designed with its own acoustic performance target

Results

results

Measurements recorded less than 50 dB(A) at 1 m on the façade, starting from internal levels exceeding 103 dB(A) inside the engine room.

Following commissioning of the plant, we carried out an acoustic acceptance test to verify the achieved results, with a fully positive outcome across all aspects.

In particular, a very high acoustic performance was required for the ventilation systems and the external wall of the cogeneration room, given the significant noise generated by the 2.6 MW engine and the proximity to the adjacent residential building.

Measurements recorded less than 50 dB(A) at 1 m on the façade, starting from internal levels exceeding 103 dB(A) inside the engine room.

A significant result achieved thanks to a two-stage intake silencer installed within a sound-absorbing duct system, ensuring an airflow rate of 140,000 m³/h through three 15 kW fans each, as well as a removable external enclosure composed of two independent walls forming a 600 mm cavity. Access to the engine room is provided through doors equipped with panic hardware.