April 18, 2017
How to soundproof a cogeneration plant? The 2Zeta intervention in Pegognaga (Mantua)
INTRODUCTION
Reference legislation:
- Law No. 447 of 26 October 1995: “Framework Law on noise pollution”
- Decree of the President of the Council of Ministers of 14 December 1997: “Determination of limit values for sound sources”.
- Decree of 16 March 1998: “Techniques for the detection and measurement of noise pollution”.
CASE HISTORY
CASE HISTORY
In 2010, a cogeneration plant (combined production of electricity and heat) was built at a large slaughterhouse in Pegognaga (MN), powered by oil obtained from animal fat derived from by-products of bovine slaughtering.
The operation of this plant, characterized by two engines with an hourly capacity of 4,200 kW electric and 4,900 kW thermal, allows for an annual production of over 336 million kWh of electricity and more than 39 million kWh of thermal energy.
Before the intervention, a predictive acoustic impact assessment was carried out in accordance with Article 8, paragraph 4 of Law 447/95. A site inspection was therefore conducted by a qualified acoustics technician in order to gather information regarding the activity performed, the expected noise sources and their location, as well as to measure the residual sound level at the identified sensitive receptors.
The plant is located in an area classified as Class IV “Areas of intense human activity” and Class III “Mixed-use areas.” The two cogeneration modules, with a declared noise level of Lp = 110 dB(A) at 1 meter, are installed inside a concrete room, a highly reverberant environment.
Our intervention, in accordance with the acoustic impact report, was designed to ensure a maximum noise level of Lp = 55 dB(A) at a distance of 10 meters.
Elements of the intervention
- Soundproof double-leaf doors with sound-insulating and sound-absorbing panels, equipped with damping layers and exposed galvanized micro-perforated sheet metal.
- Silencers for engine room ventilation, made of sound-insulating and sound-absorbing panels and acoustic baffles, installed inside the structure and arranged longitudinally along the duct. They divide and channel the airflow, facilitating the absorption of sound energy.
- Silencers for engine combustion air, equipped with high-efficiency filters.
Testing and results
During the acoustic testing, the plant was operating under normal conditions, with both units at nominal power, the boilers in operation, and all heat dissipators running. Environmental noise measurements were carried out in accordance with the Ministerial Decree of 16.03.1998 and confirmed compliance with the limits set for Class III, with no tonal components detected.
The results
We achieved the required attenuation; therefore, the testing was successfully passed.