2 Zeta is a team of 20 people who, since 1989, designs, manufactures and installs soundproofing systems for various noise sources in the industrial, environmental, civil and energy sectors.
Company address

April 18, 2017

A case of noise pollution: 2 Zeta intervention at the Enpals office in Venice

Law No. 447 of 26 October 1995, “Framework Law on noise pollution,” establishes the fundamental principles for protecting both the external environment and residential settings from noise pollution.

The Prime Ministerial Decree of 14 November 1997, implementing Law No. 447, defines the absolute daytime and nighttime limit values for noise emission and immission in outdoor environments, as well as the differential criterion within residential environments.

Absolute Emission Limit Values dB(A)

The emission limit value is the maximum level of noise that may be emitted by a sound source, measured in areas accessible to people or communities in the vicinity of the source itself (generally, the measurement is taken at the boundary of the property of the noise source and, in practice, it must be at least 5 dB(A) lower than the area limit in order to allow others to also “produce noise”).

Absolute Immission Limit Values dB(A)

The immission limit value is the maximum level of noise that may be introduced by one or more sound sources into the external environment or residential environment, measured near the receptors (it represents the sum of noise emitted by multiple different sources).

CASE HISTORY

CASE HISTORY

**CLASS III – mixed-use areas:** urban areas affected by local or through vehicular traffic, with medium population density, the presence of commercial activities and offices, with a limited presence of craft activities and no industrial activities; rural areas affected by activities involving the use of operating machinery.

The noise emission sources consisted of two air-cooled water chiller units by Daikin (VRVIII inverter model), operating during the daytime in an intermittent manner depending on system demand.

The units were installed on the terrace on the 3rd floor of the ENPALS building, Calle Emo, 1553/A in Venice.

The surrounding area is predominantly residential, with some commercial and hotel activities. The buildings are mostly 3–4 storeys high and overlook a narrow courtyard enclosed on three and a half sides out of four, making the space particularly reverberant.

The noise sources were subjected to acoustic mitigation measures consisting of a sound-insulating and sound-absorbing barrier on three sides and a sound-absorbing lining on the rear wall. In addition, at the exhaust of the fans located above the units, a soundproof enclosure was installed.

The results

After the intervention, the problem was solved; the reduction was in fact 10 dB(A), and the daytime differential criterion was complied with (ambient noise level inside residential spaces below 50 dB(A)).